Permit Number: T10CM02738
Parcel: 115072200

Address:
271 W LEE ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/WWM

Permit Number - T10CM02738
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/01/2010 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied 1. Provide a fixture unit schedule for the entire property (including existing) for the water supply system with appropriate fixture unit values, UPC Tables 6-5.

2. Provide the maximum developed length of water line from the meter the furthest appliance served, the size of the water meter, the lowest available pressure, and the diameter of the water supply line from the meter, UPC Table 6-6.
11/22/2010 DROBEY1 ZONING REVIEW Needs Review
11/22/2010 DROBEY1 NPPO REVIEW Needs Review
11/22/2010 DROBEY1 WWM REVIEW Needs Review
11/22/2010 DROBEY1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/22/2010 DELMA ROBEY OUT TO CUSTOMER Completed