Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM02721
Parcel: 13332013J

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T10CM02721
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/03/2010 RONALD BROWN ADA REVIEW Passed
11/04/2010 DAVE MANN FIRE REVIEW Approved
11/05/2010 RONALD BROWN ZONING HC REVIEW Denied Reference Building Comments
11/05/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. SHEET T-1:
a. The building Data Summary shows 2 accessible spaces are to be available and the site plans shows only one.
2. Provide structural calculations for all roof top mounted HVAC units,
3. Provide a letter to the Building Official listing all deferred submittal items.
4. This project is governed by the 2006 IBC which requires all accessibility requirements to be as per Chapter 11 and ICC (ANSI 117.1). Please remove all references through out all drawings to ADA and substitute the accessible code requirement above.
5. Please show on the seating all accessible seating as required by Sections 1108.2.8 and ICC (ANSI 117.1), Section 902.
6. Please show all construction details concerning the Patio Cover on the drawings including structural foundation and framing plans and calculations. The spec data booklet included with this submittal is for a trellised unit attached to the building whereas the one shown here is a 4 column, free standing structure.
7. Provide all Special Inspection Certifications as per 2006 IBC, Sections 106 and 1704. A list of inspections has been added to the Conditions menu. Please review list and provide in writing any changes.
END OF REVEIW

END OF REVIEW
11/05/2010 LOREN MAKUS ENGINEERING REVIEW Denied The site plan must be approved before the building plans are approved.
11/05/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
11/16/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The applicable code for all commercial plumbing projects is the 2006 Uniform Plumbing Code with Local Amendments. The plumbing sheets indicate that the activity has been designed per the 2006 UPC but the architectural sheet, T-1 is referencing the 2006 IPC. Provide an approved appeal to the building official if the plans are to be reviewed to the 2006 IPC.
2. Appliances (e.g. ovens, coffee brewers, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Table 6-3, UPC 2006 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 602.3, 603.0, and Table 6-2, UPC 2006.
3. Coordinate the size of the water meter serving the building; the civil drawings indicate a 1-1/2" meter compared to the 1" meter referenced on the plumbing plans. Reference: Section 103.2.3, UPC 2006.
4. Provide size information for the roof scuppers, downspouts, and overflow scuppers (referenced detail 8/A-9 is not shown). Reference: Section 1101.11, UPC 2006.
5. Coordinate with the architectural drawings. The architectural backgrounds are different (A-1), the water heater does not need a flue (A-4), and the "optional floor drain" (3/A-3) is not on the plumbing sheets. Reference: Section 103.2.3, UPC 2006.
11/16/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify the need for providing a flue for an electric water heater. Reference: Section 106.3.1, IMC 2006.
2. Provide energy code compliance calculations (using Pima County < 4,000 feet). Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.
3. Specify the construction of the exhaust duct for KH-1. Reference: Section 506.4, IMC 2006.
4. Provide structural calculations and details to show that the Type II hood is supported from the building structure in accordance with Section 507.6, IMC 2006. Reference: Section 302.1, IMC 2006.
5. The required exhaust rate for a Type II hood used for cooking operations is determined by the exhaust rate for the light-duty appliances under a Type I hood. Reference: Section 507.13.4, IMC 2006.
11/16/2010 ROBERT SHERRY WATER REVIEW Approved
11/23/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
11/29/2010 GERRY KOZIOL WWM REVIEW Denied NEED REVIEW/APPROVAL FOR CAPACITY EVALUATION AND/OR POINT OF CONNECTION (PCRWRD DEV LIAISON UNIT) 3RD FL PWB- 740-6534.
ISSUED WITH 750 GAL GREASE INTERCEPTOR
12/01/2010 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: 9485 E. Broadway
T10CM02721
Building Plan (1st Review)

TRANSMITTAL DATE: December 1, 2010

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning can not approve the building plan until the site plan has been approved.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t10cm02721.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED:

Final Status

Task End Date Reviewer's Name Type of Review Description
12/02/2010 CPIERCE1 OUT TO CUSTOMER Completed
12/02/2010 SUE REEVES REJECT SHELF Completed