Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T10CM02719
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/04/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 10/04/2010 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 10/04/2010 | ROBERT SHERRY | WATER | REVIEW | Denied | Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. Provide a letter from Tucson Water approving the proposed location for the backflow preventer. Reference: COT Backflow Prevention Ordinance, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf |
| 10/05/2010 | DAVE MANN | FIRE | REVIEW | Denied | Fire Comments: Location map shows wrong location. Show nearest fire hydrant. If hose lay is greater than 300 feet to rear of building a new hydrant or sprinklers are required. |