Permit Number: T10CM02719
Parcel: 122124060

Address:
1627 N SWAN RD

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T10CM02719
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/04/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/04/2010 GERRY KOZIOL WWM REVIEW Approved
10/04/2010 ROBERT SHERRY WATER REVIEW Denied Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. Provide a letter from Tucson Water approving the proposed location for the backflow preventer. Reference: COT Backflow Prevention Ordinance, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf
10/05/2010 DAVE MANN FIRE REVIEW Denied Fire Comments:

Location map shows wrong location.
Show nearest fire hydrant. If hose lay is greater than 300 feet to rear of building a new hydrant or sprinklers are required.