Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/04/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
10/04/2010 | GERRY KOZIOL | WWM | REVIEW | Approved | |
10/04/2010 | ROBERT SHERRY | WATER | REVIEW | Denied | Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. Provide a letter from Tucson Water approving the proposed location for the backflow preventer. Reference: COT Backflow Prevention Ordinance, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf |
10/05/2010 | DAVE MANN | FIRE | REVIEW | Denied | Fire Comments: Location map shows wrong location. Show nearest fire hydrant. If hose lay is greater than 300 feet to rear of building a new hydrant or sprinklers are required. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/05/2010 | DELMA ROBEY | REJECT SHELF | Completed |