Permit Number: T10CM02700
Parcel: 13629003A

Review Status: Active

Review Details: RESUBMITTAL

Permit Number - T10CM02700
Review Name: RESUBMITTAL
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
09/23/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Prior to permit issuance, the Site Development plan must be approved.
2. Have the special inspection certifications been submitted for approval? There are none submitted with this resubmittal. If not, please submit certifications for approval when permit is ready to be picked up.
3. Having the building constructed on top of a property line is not compliant. Either provide a one hour wall down the middle of the property line or obtain a lot combo.
END OF REVIEW
09/26/2011 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Clements Senior Center
T10CM02700
Building Plan (3rd Review)

TRANSMITTAL DATE: September 27, 2011


1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning can not approve the building plan until the site plan has been approved.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t10cm02700.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED:
10/04/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Remove all Photovoltaic Plans from the drawings .

Ray T Majuta,
Elect Pln CK,
PDSD, C of Tucson,
10/05/2011
Ray.majuta@tucsonaz.gov
10/04/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
10/11/2011 PAUL MACHADO ENGINEERING REVIEW Denied The bldg. plans cannot be approved prior to the submittal and approval of a flood plain use permit.
10/18/2011 GERRY KOZIOL WWM REVIEW Denied need capacity evaluation - By PCRWRD 3RD FLOOR - KURT STEMM 740-6607
NEED TO PROVIDE APPROVED COPY OF EXSISTING ON-SITE PRIVATE SEWER FOR BASE MAP
NEED WW/IWC REVIEW & APPROVAL OF 750 GAL GREASE INTERCEPTOR BY TOM TOMCHAK - 5025 W INA RD - 443-6200

Final Status

Task End Date Reviewer's Name Type of Review Description
10/21/2011 SUE REEVES REJECT SHELF RECEIVED