Permit Number: T10CM02700
Parcel: 13629003A

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T10CM02700
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/30/2010 MARTIN BROWN FIRE REVIEW Approved
09/30/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Needs Health Departmwent review.
2. Provide structural calculations for cistern and cistern foundatuions, Roof mounted HVAC units and lighting pole foundations.
SHEETS A2.1 AND DETAIL 1/A4.1:
3. Provide door to men's accessible toilet stall
4. Reverse swing of women's toilet stall door
SHEET A3:
5. Recalculate occupany load using A3 for front assembly. Recalculate toilet fixture count and change toilets as required.
SHEET A4.1
6. Generic details are not acceptable. Please merge the toilet elevations with the generic code copied details.
7. Please identify the "x" in a square, in a square loacted on the outside of the women's toilet room door on the strike side.
8. Please provide a "Cow's Tonge" detail. The architectural drawings reference to the mechanical drawings, the mechanical drawings reference to the plumbing drawings which reference back to the architectural drawings which references to the landscape drawings which again references to the architectural drawings.
9. Please provide a detail for roof top drainage to the cisterns. Reference mechanical comments.
STRUCTURAL FOUNDATION AND FRAMING COMMENTS

STRUCTURAL DESIGN REVIEW
T10CM02700
CLEMENTS SENIOR CENTER

10. SHEET S0.1; FOUNDATION NOTES: NOTE 1 INDICATES THE FOUNDATION DESIGN IS PRELIMINARY. REVISE.
11. SHEET S0.1; FOUNDATION NOTES: PROVIDE A COPY OF THE ORIGINAL (AUGUST 18, 2003) GEOTECHNICAL REPORT. THIS UPDATE (FEBRUARY 5, 2010) DOES NOT PROVIDE ADEQUATE INFORMATION TO REVIEW THE FOUNDATION DESIGNS.
12. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.


END OF REVIEW
10/04/2010 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: PROJECT: Clements Senior Center
T10CM02700
Building Plan (1st Review)

TRANSMITTAL DATE: October 4, 2010


1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning can not approve the building plan until the site plan has been approved.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t10cm01281.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED:
10/04/2010 RONALD BROWN ZONING HC REVIEW Passed This is a COT owned project. Reference ADA folder foer accessibility comments
10/04/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/04/2010 RONALD BROWN ADA REVIEW Denied Reference Building Comments
10/07/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The applicable code for all commercial plumbing projects is the 2006 Uniform Plumbing Code with Local Amendments. Provide an approved appeal to the building official if the plans are to be reviewed to the 2006 IPC.
10/07/2010 ROBERT SHERRY WATER REVIEW Approved
10/08/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/20/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project:T10CM02700
Clements Senior Center
8155 E Poinciana Dr

Electrical plans denied for following:
1. 2006 IECC Lighting Budget Calculations required.
2. Structural mounting of PV Modules is required, cannot find any information on this?
3. Need to provide Specifications sheets for PV components, inverter, modules combiner box, etc.
4. Will the inverter and associated equipment be located next to service area?
5. Show calculations for PV system concerning DC side ,(voltages and current).
6. Show grounding required for modules.

Ray Majuta,PDSD,City of Tucson,
Elect Plan Ck,
10/21/10
Ray.Majuta@tucsonaz.gov
10/21/2010 PAUL MACHADO ENGINEERING REVIEW Denied The bldg. plans cannot be approved prior to the submittal of the flood plain use permit.
10/26/2010 GERRY KOZIOL WWM REVIEW Denied need capacity evaluated & location/method of connection approved by (PCRWRD DEVELOPMENT LIAISON UNIT) 3RD FLOOR 740-6534
NEED TO PROVIDE APPROVED COPY OF LOCATION & METHOD CONNECTION TO SEWER FOR BASE MAP UPDATE

Final Status

Task End Date Reviewer's Name Type of Review Description
03/22/2011 SUE REEVES APPROVAL SHELF Completed
03/22/2011 CPIERCE1 OUT TO CUSTOMER Completed