Permit Number: T10CM02694
Parcel: 14117007Q

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM02694
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/28/2010 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Snap Fitness
T10CM02694
Building Plan (1st Review)

TRANSMITTAL DATE: September 28, 2010

1. Provide a complete vehicle parking space calculation for the entire site on the cover sheet.

2. Reference the Development Plan number D04-0019 on the cover sheet.


If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t10cm02694.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED:
09/28/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top unit. Reference: Section 302.1, IMC 2006
09/28/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
09/28/2010 ROBERT SHERRY WATER REVIEW Approved
09/28/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A1: WITH THE NEW SQUARE FOOTAGE AND THE NEW OCCUPANT LOAD (4588 SF AND 92 OCCUPANTS), TWO RESTROOMS ARE REQUIRED FOR BOTH MEN AND WOMEN (SEE IBC TABLE 2902.1). 46 MALE AND 46 FEMALE OCCUPANTS REQUIRE TWO RESTROOMS EACH (ONE PER 25 FOR THE FIRST 50). REVISE.
09/28/2010 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
09/28/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
09/28/2010 DAVE MANN FIRE REVIEW Approved
09/28/2010 ERIC NEWCOMB ADA REVIEW Passed
09/28/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
09/28/2010 ERIC NEWCOMB ZONING HC REVIEW Approved
09/30/2010 CPIERCE1 ENGINEERING REVIEW Needs Review