Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM02653
Parcel: 11711076A

Address:
126 E ALAMEDA ST

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T10CM02653
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/23/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
09/23/2010 PAUL MACHADO ENGINEERING REVIEW Approved
09/23/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
09/23/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PROVIDE STRUCTURAL CALCULATIONS INDICATING THE EXISTING STRUCTURE AT THE THIRD FLOOR IS ADEQUATELY SIZED FOR THE NEW MECHANICAL LOADS.
09/23/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations demonstrating adequate ventilation. Reference: Section 403.3, IMC 2006.
2. Show the size and routing of the condensate drains. Reference: Section 307.2, IMC 2006 and Section 814.0, UPC 2006.
09/23/2010 MARTIN BROWN FIRE REVIEW Approved
09/23/2010 DAVID RIVERA ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/23/2010 CINDY AGUILAR OUT TO CUSTOMER Completed