Permit Number: T10CM02648
Parcel: 116183810

Address:
325 N GRANDE AV

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T10CM02648
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/04/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. The foundation references detail 7/A1. Where is it?
2. Where is Keynote 6 referenced?
3. At Framing Notes 1, change the reference to the 2006 IBC.
4. At detail 6, the footing width is called out as 3'-0" where the structural calculations call out for a 3'-6" square footing. Please reconcile.
END OF REVIEW