Permit Number: T10CM02648
Parcel: 116183810

Address:
325 N GRANDE AV

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T10CM02648
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/05/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/06/2010 RONALD BROWN ZONING HC REVIEW Passed
10/07/2010 MARTIN BROWN FIRE REVIEW Approved
10/07/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please provide structural foundation calculations for the 8'0" high fence.
2. The two fabric structures and the 1 ramada structures appear to be deferred submittals.
a. Please provide a letter summary of all the deferred submittals and send to the Building Offical, Mr. Ron Boose, for additional fee accessment.
b. Insure structural foundation details and calculations are included with submittal.
END OF REVIEW
10/08/2010 RONALD BROWN ADA REVIEW Passed Shade structure only. For site accessibility comments reference SITE work flow.
10/13/2010 STEVE SHIELDS ZONING REVIEW Approved
10/13/2010 ELIZABETH LEIBOLD ENGINEERING REVIEW Approved Menlo Park at Grande & Fresno - approved. See T10CM01080-R. Engineering reviewed at counter with Zoning & consultant 13OCT10. EL
10/19/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. A permanently legible imprint of the registrant's seal and signature, along with the date the documents were sealed, shall appear on each sheet of the project drawings. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Sheet IR1.01 indicates that the existing potable water service pipe for the pool is being tapped to provide potable water service to the future restroom building. Provide the size of the existing pipe, the size of the new pipe, and the anticipated potable water demand for the restroom. Reference: Sections 103.2.3 and 610.1, UPC 2006.
10/19/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
10/19/2010 RSHERRY1 WWM REVIEW Passed No sewer-connected fixtures.
10/19/2010 ROBERT SHERRY WATER REVIEW Denied 1. Show the location of the reduced pressure backflow assembly on the drawings and indicate the size of the assembly. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code.
2. Show the location and size of the potable water meter currently planned to service the proposed restroom for Menlo Park. Indicate the current demand on this meter.
11/04/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/09/2010 CPIERCE1 OUT TO CUSTOMER Completed