Permit Number: T10CM02596
Parcel: 13623008Q

Address:
3455 S WILMOT RD

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T10CM02596
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/17/2010 MARTIN BROWN FIRE REVIEW Approved
09/24/2010 MICHAEL WYNEKEN PLANNING-CITY HALL REVIEW Denied Add note regarding hours of generator testing.
09/27/2010 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: T10CM02596
3455 s Wilmot Road (1st Review)

TRANSMITTAL DATE: September 27, 2010

1. The Cell Tower plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. The plan must be approved and stamped by the Special Exception Section prior to approval by Zoning.

3. Zoning will re-review the Cell Tower plan on the next submittal to insure compliance with the approved Special Exception process. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\celltower\t10cm02596.doc
09/29/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Provide complete structural calculations for:
a. 8" concrete slab
b. 8' hugh RCMU wall
c. Specify exact psi of concrete used for calculations and revise note 3 sheet A-3 to that specification.
2. Please provide Special Inspection Certifications for:
a. Concrete 3,000 psi or above
b. Expansion anchors
c. Any others as deemed necessary by the project structural engineer.
END OF REVIEW
09/30/2010 LOREN MAKUS ENGINEERING REVIEW Approved
10/04/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Denied,see comments for Activity T10CM02594

Ray T Majuta
Elect Plan Ck
10/05/10

Final Status

Task End Date Reviewer's Name Type of Review Description
02/17/2011 SUE REEVES OUT TO CUSTOMER Completed
02/17/2011 SUE REEVES REJECT SHELF Completed