Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T10CM02595
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/17/2010 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 09/24/2010 | MICHAEL WYNEKEN | PLANNING-CITY HALL | REVIEW | Denied | Add notes regarding hours of generator testing, and painting of equipment - per conditions of approval. |
| 09/27/2010 | STEVE SHIELDS | ZONING | REVIEW | Denied | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: T10CM02595 2190 E. Benson Hy. (1st Review) TRANSMITTAL DATE: September 27, 2010 1. The Cell Tower plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. The plan must be approved and stamped by the Special Exception Section prior to approval by Zoning. 3. Zoning will re-review the Cell Tower plan on the next submittal to insure compliance with the approved Special Exception process. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 C:\planning\celltower\t10cm02595.doc |
| 09/29/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Provide complete structural calculations for: a. 8" concrete slab b. 8' hugh RCMU wall c. Specify exact psi of concrete used for calculations and revise note 3 sheet A-3 to that specification. 2. Please provide Special Inspection Certifications for: a. Concrete 3,000 psi or above b. Expansion anchors c. Any others as deemed necessary by the project structural engineer. END OF REVIEW |
| 09/30/2010 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 10/04/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Denied, see comments for Activity T10CM02594 Ray T Majuta Elect Pln CK 10/05/10 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/25/2010 | SUE REEVES | OUT TO CUSTOMER | Completed |
| 10/25/2010 | SUE REEVES | REJECT SHELF | Completed |