Address:
5350 E GLENN ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM02594
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/24/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T10CM02594, 5350 E Glenn St


Talked to Jennifer Bello from JRA & Associates, previous two reviews have requested the information sheets (cut sheets) on the ReLi On unit to be used. This information is required in order to review how the information on the plans relates to the equipment.
Describe to what will this power system be connected regarding the equipment on site, voltage , current etc.

Ray T Majuta,
PDSD, City of Tucson,
Elect Plan Ck,
11/22/10