Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T10CM02594
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/17/2010 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 09/24/2010 | MICHAEL WYNEKEN | PLANNING-CITY HALL | REVIEW | Denied | Add notes regarding generator test times and equipment painting requirements, per conditions b,c,and d. |
| 09/27/2010 | STEVE SHIELDS | ZONING | REVIEW | Denied | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: T10CM02594 5350 E. Glenn Street (1st Review) TRANSMITTAL DATE: September 27, 2010 1. The Cell Tower plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. The plan must be approved and stamped by the Special Exception Section prior to approval by Zoning. 3. Zoning will re-review the Cell Tower plan on the next submittal to insure compliance with the approved Special Exception process. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 C:\planning\celltower\t10cm02594.doc |
| 09/29/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Provide complete structural calculations for: a. 8" concrete slab b. 8' hugh RCMU wall c. Specify exact psi of concrete used for calculations and revise note 3 sheet A-3 to that specification. 2. Please provide Special Inspection Certifications for: a. Concrete 3,000 psi or above b. Expansion anchors c. Any others as deemed necessary by the project structural engineer. END OF REVIEW |
| 09/30/2010 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 10/04/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project:T10CM02594 5350 E Glenn Installation of Hydrogen Fuel Cell . & Storage Cabinet Electrical denied for the following: The 2005 NEC, Section 692.6 reads that" the fuel cell systems shall be evaluated and listed for its intended application prior to installation." In order for me to evaluate the system I need for you to provide information on the Reli/On Hydrogen Fuel Cell System, provide cut sheets giving such items as Size in KW,output voltage and current,over-current protection , a one line diagram, Nema rating of equipment if used outdoors ,grounding requirements of equipment --- etc. 2. Provide on plan notation that installer is to comply with signage required by NEC 2005, 692.17 and 692.56. Ray T Majuta, PDSD, City of Tucson, Elect Plan Review, 10/05/10 Ray.Majuta@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/25/2010 | SUE REEVES | OUT TO CUSTOMER | Completed |
| 10/25/2010 | SUE REEVES | REJECT SHELF | Completed |