Permit Number: T10CM02581
Parcel: 116094370

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM02581
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/15/2010 LOREN MAKUS ENGINEERING REVIEW Approved
11/15/2010 DAVE MANN FIRE REVIEW Denied Fire Comments:
Per IFC Section 503.1.1, building must be within 150' of fire apparatus access road. Additionally, slope of road is too steep to allow access. Square footage requires additional fire protection water supply.

Therefore, fire sprinklers are required.
11/16/2010 ANDREW CONNOR NPPO REVIEW Approved
11/24/2010 SEPTIC APPROVAL WWM REVIEW Approved
11/29/2010 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Approved
11/29/2010 KEN VAN KARSEN BUILDING-COMMERCIAL REVIEW Approved
11/30/2010 MICHAEL ST. PAUL ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/07/2010 CPIERCE1 OUT TO CUSTOMER Completed
12/07/2010 SUE REEVES REJECT SHELF Completed