Permit Number: T10CM02528
Parcel: 10705126E

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM02528
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/10/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
11/10/2010 ROBERT SHERRY WATER REVIEW Approved
11/10/2010 RONALD BROWN HC REVIEW Approved
11/15/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not resolved. Provide cleanouts sized per Section 707.11, UPC 2006. A cleanout is required at the junction of the building drain and the building sewer per Section 719.1, UPC 2006 but the building sewer in this case is 4" which will require a minimum cleanout size of 3-1/2", not 3" as shown.
2. Comment not resolved. The section of vent between the laundry and the restroom is required to be one pipe-diameter larger than required by Table 7-5, UPC 2006 due to the long horizontal run. The maximum length of the horizontal portion of a 2" vent is 40-feet unless the vent has been oversized by one pipe diameter for its entire length.
11/22/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
11/23/2010 DAVID RIVERA ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/24/2010 SUE REEVES APPROVAL SHELF Completed
11/24/2010 SUE REEVES OUT TO CUSTOMER Completed