Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T10CM02528
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/10/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
11/10/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
11/10/2010 | RONALD BROWN | HC | REVIEW | Approved | |
11/15/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not resolved. Provide cleanouts sized per Section 707.11, UPC 2006. A cleanout is required at the junction of the building drain and the building sewer per Section 719.1, UPC 2006 but the building sewer in this case is 4" which will require a minimum cleanout size of 3-1/2", not 3" as shown. 2. Comment not resolved. The section of vent between the laundry and the restroom is required to be one pipe-diameter larger than required by Table 7-5, UPC 2006 due to the long horizontal run. The maximum length of the horizontal portion of a 2" vent is 40-feet unless the vent has been oversized by one pipe diameter for its entire length. |
11/22/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
11/23/2010 | DAVID RIVERA | ZONING | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/24/2010 | SUE REEVES | APPROVAL SHELF | Completed |
11/24/2010 | SUE REEVES | OUT TO CUSTOMER | Completed |