Permit Number: T10CM02487
Parcel: 13401002D

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM02487
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/07/2010 STEVE SHIELDS ZONING REVIEW Approved
09/07/2010 PAUL MACHADO ENGINEERING REVIEW Approved
09/08/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
09/08/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show how the hood supports are to be connected to the building structure (i.e. show the structural engineers design on the drawings). Reference: Sections 302.1 and 507.6, IMC 2006.
2. Provide the materials of construction for the wall adjacent to the hood. Reference: section 507.9, IMC 2006.
3. Show that the termination of the exhaust outlet complies with the requrements of Section 506.3.12.3 (exception), IMC 2006.
4. Revise the grease duct velocity to a minimum of 1500 FPM. Reference: Section 506.3.4, IMC 2006, as amended by the city of Tucson. Note that the exhaust flow rate is shown as 800 CFM and 600 CFM on sheet M1.1, and 805 CFM on the Captiveair shop drawings.
5. Provide a specification for the rond grease duct. Clarify the need for Firemaster Fastwrap if the round duct is listed for zero-clearance installation.
09/08/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/08/2010 ROBERT SHERRY WATER REVIEW Approved
09/08/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
09/08/2010 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
09/08/2010 MARTIN BROWN FIRE REVIEW Approved
09/08/2010 ERIC NEWCOMB ADA REVIEW Passed
09/08/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/08/2010 ERIC NEWCOMB ZONING HC REVIEW Passed