09/17/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10CM02467
405 E Wetmore Rd


The Electrical Plans have been denied for the following:

1. The existing CT enclosure is marked 600 Amps, should be
1600 Amps.
2. NEC 2005 Ordinance # 10417, Section 230.90 A, Except #6. The sum ratings of the circuit breakers or fuses shall be permitted to exceed the ampacity of the service entrance conductors provided the calculated load in accordance with Article 220 does not exceed the ampacity of the serviice conductors.. Sheet E2.0 just indicates " existing 1600 Amp Secondary to remain". The total value of the overcurrent devices could total 2100 Amps. What size are the service entrance conductors ?
3. Will the new 400 Amp service Main be seperated by not less than 2 feet,but grouped ?
4. The existing AC-1 unit appears to draw 28.7 Amps , connected to a 20 Amp breaker ?



Ray T Majuta,
Elect Pln CK, PDSD,
City of Tucson,
9/19/10