Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/07/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 3/32-inch. Reference: Section 106.1.1, IBC 2006. 2. Appliances (e.g. beverage dispensers, ice makers, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Table 6-3, UPC 2006 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 602.3, 603.0, and Table 6-2, UPC 2006. 3. Clarify the drainage arrangement for the 3-compartment pot sink. The waste and vent riser diagram, the waste and vent plan, and detail 6/P-4.0 appear to correctly show a direct-connection for two compartments and an indirect-connection for one compartment but the Fixture Unit Schedule (P-1.0) and the Kitchen Equipment Schedule (P-2.0) indicate only an indirect-connection. Reference: Sections 304.0, 704.3, and 801.2.3, UPC 2006. 4. The natural gas load for the Chinese range is shown as 500 MBH, 590 MBH, and 610 MBH on drawings K-1.0, P-1.0, P-3.0; except for the 500 MBH load shown on sheet K-1.0, the branch piping to the range is under-sized. (Note that a cubic foot of natural gas supplied in Tucson has approximately 1000 BTU) Revise the size of the natural gas pipe per Section 402.3, IFGC 2006. |
09/08/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Clarify how the installation of two microwave ovens without a Type II hood is justified. Reference: Section 507.2.2 (3), IMC 2006. |
09/23/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/29/2010 | CPIERCE1 | OUT TO CUSTOMER | Completed |
09/29/2010 | SUE REEVES | REJECT SHELF | Completed |