Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T10CM02451
Parcel: 12801005H

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM02451
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/07/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 3/32-inch. Reference: Section 106.1.1, IBC 2006.
2. Appliances (e.g. beverage dispensers, ice makers, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Table 6-3, UPC 2006 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 602.3, 603.0, and Table 6-2, UPC 2006.
3. Clarify the drainage arrangement for the 3-compartment pot sink. The waste and vent riser diagram, the waste and vent plan, and detail 6/P-4.0 appear to correctly show a direct-connection for two compartments and an indirect-connection for one compartment but the Fixture Unit Schedule (P-1.0) and the Kitchen Equipment Schedule (P-2.0) indicate only an indirect-connection. Reference: Sections 304.0, 704.3, and 801.2.3, UPC 2006.
4. The natural gas load for the Chinese range is shown as 500 MBH, 590 MBH, and 610 MBH on drawings K-1.0, P-1.0, P-3.0; except for the 500 MBH load shown on sheet K-1.0, the branch piping to the range is under-sized. (Note that a cubic foot of natural gas supplied in Tucson has approximately 1000 BTU) Revise the size of the natural gas pipe per Section 402.3, IFGC 2006.
09/08/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Clarify how the installation of two microwave ovens without a Type II hood is justified. Reference: Section 507.2.2 (3), IMC 2006.
09/23/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/29/2010 CPIERCE1 OUT TO CUSTOMER Completed
09/29/2010 SUE REEVES REJECT SHELF Completed