Review Details: RESUBMITTAL

Permit Number - T10CM02445
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/15/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the submitted ventilation calculations to comply with the requirements of Section 403.3, IMC 2006, as amended by the City of Tucson. The calculations may be based on either Table 403.3, IMC 2006 (which includes Section 403.3.2) or ASHRAE 62.1-2004 using the default occupancy rate in Table 6-1.
10/18/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The specified drinking fountain (Elkay EZ4) does not meet the accessibility requirements as shown in Section 1109.5, IBC 2006. (See also Section 602.4, ICC/ANSI A117.1-2003.)
2. Provide the listing information for the specified mixing valve (Symmons 5-130 Thermixer). All plumbing fixtures, fittings, and devices shall be listed or labeled by a nationally-recognized, accredited conformity assessment company (e.g. UL, ETL, UPC, etc). Reference: Section 301.1.1, UPC 2006.
3. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Show also how the platform is to be attached to the wall. Reference: Sections 310.0 and 314.5, UPC 2006.
4. Provide a vacuum relief for the storage-type water heater located above the fixture outlets. Reference: Section 608.7, UPC 2006.
10/19/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/26/2010 GERARDO BONILLA OUT TO CUSTOMER Completed
10/26/2010 SUE REEVES REJECT SHELF Completed