Permit Number - T10CM02445
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/15/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the submitted ventilation calculations to comply with the requirements of Section 403.3, IMC 2006, as amended by the City of Tucson. The calculations may be based on either Table 403.3, IMC 2006 (which includes Section 403.3.2) or ASHRAE 62.1-2004 using the default occupancy rate in Table 6-1. |
| 10/18/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The specified drinking fountain (Elkay EZ4) does not meet the accessibility requirements as shown in Section 1109.5, IBC 2006. (See also Section 602.4, ICC/ANSI A117.1-2003.) 2. Provide the listing information for the specified mixing valve (Symmons 5-130 Thermixer). All plumbing fixtures, fittings, and devices shall be listed or labeled by a nationally-recognized, accredited conformity assessment company (e.g. UL, ETL, UPC, etc). Reference: Section 301.1.1, UPC 2006. 3. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Show also how the platform is to be attached to the wall. Reference: Sections 310.0 and 314.5, UPC 2006. 4. Provide a vacuum relief for the storage-type water heater located above the fixture outlets. Reference: Section 608.7, UPC 2006. |
| 10/19/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/26/2010 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 10/26/2010 | SUE REEVES | REJECT SHELF | Completed |