| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/07/2010 | DAVE MANN | FIRE | REVIEW | Approved | |
| 09/14/2010 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 09/14/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/14/2010 | RONALD BROWN | ZONING HC | REVIEW | Approved | |
| 09/15/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006. 2. Provide calculations demonstrating adequate ventilation. Reference: Section 403.3, IMC 2006. |
| 09/15/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide plumbing plans for the new work, including water isometrics and waste and vent isometrics. Reference: Section 103.2.3, UPC 2006. 2. The specified drinking fountain does not meet the accessibility requirements as shown in Section 1109.5, IBC 2006. 3. Provide the minimum plumbing facilities required by Table 2902.1, IBC 2006, for mercantile occupancy (e.g. service sink). 4. Given the temperature range of the water supply in Tucson (as high as 90.3 degrees Fahrenheit), specify how the instantaneous water heater that delivers a 41degree Fahrenheit rise to the lavatory faucet can guarantee a maximum delivery temperature of 110 degrees Fahrenheit. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006. 5. Provide water pressure and water pipe sizing calculations. Clarify how the ¾" water service is connecting to a 1" water supply for the restrooms. (Note also that the specified water heater has a minimum pressure requirement of 25 PSI.) Reference: Section 610.1, UPC 2006. |
| 09/15/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/21/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T10CM02445 7101 E Broadway Bl T I Retail Electrical pland denied for following: 1. As per City of Tucson Submittal Requirements, Lighting Budget Load Calculations required for interior per 2006 IECC. Com Check ok. 2. See Mechanical Plans Examiner's denial, the exhaust fan in the restrooms to be set to exhaust any coditioned air supplied in, the wiring only energizes fan only when light energized. Ray T Majuta PDSD, City of Tucson, Elect Pln Ck 9/21/10 Ray.Majuta@tucsonaz.gov |
| 09/27/2010 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/08/2010 | SUE REEVES | OUT TO CUSTOMER | Completed |