Permit Number: T10CM02445
Parcel: 133224970

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM02445
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/07/2010 DAVE MANN FIRE REVIEW Approved
09/14/2010 MICHAEL ST. PAUL ZONING REVIEW Approved
09/14/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
09/14/2010 RONALD BROWN ZONING HC REVIEW Approved
09/15/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006.
2. Provide calculations demonstrating adequate ventilation. Reference: Section 403.3, IMC 2006.
09/15/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide plumbing plans for the new work, including water isometrics and waste and vent isometrics. Reference: Section 103.2.3, UPC 2006.
2. The specified drinking fountain does not meet the accessibility requirements as shown in Section 1109.5, IBC 2006.
3. Provide the minimum plumbing facilities required by Table 2902.1, IBC 2006, for mercantile occupancy (e.g. service sink).
4. Given the temperature range of the water supply in Tucson (as high as 90.3 degrees Fahrenheit), specify how the instantaneous water heater that delivers a 41degree Fahrenheit rise to the lavatory faucet can guarantee a maximum delivery temperature of 110 degrees Fahrenheit. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
5. Provide water pressure and water pipe sizing calculations. Clarify how the ¾" water service is connecting to a 1" water supply for the restrooms. (Note also that the specified water heater has a minimum pressure requirement of 25 PSI.) Reference: Section 610.1, UPC 2006.
09/15/2010 ROBERT SHERRY WATER REVIEW Approved
09/21/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10CM02445
7101 E Broadway Bl
T I Retail

Electrical pland denied for following:

1. As per City of Tucson Submittal Requirements, Lighting Budget Load Calculations required for interior per 2006 IECC. Com Check ok.
2. See Mechanical Plans Examiner's denial, the exhaust fan in the restrooms to be set to exhaust any coditioned air supplied in, the wiring only energizes fan only when light energized.


Ray T Majuta
PDSD, City of Tucson,
Elect Pln Ck
9/21/10
Ray.Majuta@tucsonaz.gov
09/27/2010 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/08/2010 SUE REEVES OUT TO CUSTOMER Completed