Permit Number: T10CM02427
Parcel: 108214240

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM02427
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/01/2010 MICHAEL ST. PAUL ZONING REVIEW Approved
09/01/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide balancing data for the HVAC air distribution system.
09/01/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
09/01/2010 ROBERT SHERRY WATER REVIEW Approved
09/01/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/01/2010 BIANCA RAMIREZ ENGINEERING REVIEW Approved
09/01/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Coordinate the water heater requirements with the electrical drawings.
2. Clarify General Note #10.
3. Revise the size of the waste line from the water closets to a minimum of 3".
4. Clarify the specifications for the water closets; flush valve or pressure-assisted tank, wall-mounted or floor-mounted?
09/01/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/01/2010 ERIC NEWCOMB ADA REVIEW Passed
09/01/2010 ERIC NEWCOMB ZONING HC REVIEW Approved
09/02/2010 GBONILL1 WWM REVIEW Needs Review
09/02/2010 GBONILL1 FIRE REVIEW Needs Review