Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM02365
Parcel: 12713036G

Address:
5910 E 5TH ST 02

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T10CM02365
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/30/2010 DAVE MANN FIRE REVIEW Denied Fire Comments:

Panic hardware is required. See sheet A1 and IFC Chapter 10.

Please include the following fire sprinkler design criteria on the sealed plans.
1. Flow data (static pressure, residual pressure, GPM)
Available from the Fire Department (520) 837-7029 or 837-7030.
2. The hazard classification of the building, including any special hazards.
3. The density required of the water supply.
09/08/2010 RONALD BROWN HC REVIEW Denied Reference Building Comments
09/08/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please provide hardware set number 8.
2. Please insure all panic hardware is installed on all required doors as per 2006 IBC, Section 1108.1.9.
3. Sheet C1 and A1
a. It is stated that panic hardware is not required for an occupancy less than 50. The occupancy load is stated as 87. Please clarify and rectify conflict.
b. Occupancy load calculations between these two sheets are not in concert. Please clarify and correct conflict.
4. Please provide accessible drinking fountains as per 2006 IBC, Section 1109.5.1 and ICC (ANSI), Section 602.
5. Please provide large scale toilet plans for all different types of toilet room layouts and include all required accessibility requirements and dimensions and clearances.
6. Please provide a detail of the Foyer Service Counter and show accessibility as per ICC (ANSI), section 9.
7. Please provide structural connection details and calculations for all roof top mounted HVAC equipment.
8. Please provide structural connection details and calculations for water heater.
9. The multi purpose room counter top sink may be not higher than 34" a.f.f. as per ICC (ANSI), Section 606.3.
10. Detail 2/S1 calls for a 10" thick footing, whereas the calculations call for 18". Please clarify and correct the conflict.
11. Calculations for the building corner footing calls for a 2' square. This is not shown on the foundation plan.
12. Please provide a deferred submittal correspondence to the Building Official for additional fee assessment.
13. Please provide Special Inspections certifications for all required special inspections as per 2006 IBC, Section 1704.
END OF REVIEW
09/13/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The applicable code for all commercial plumbing projects is the 2006 Uniform Plumbing Code with Local Amendments. Provide an approved appeal to the building official if the plans are to be reviewed to the 2006 IPC. (Sheet C1 refers to the UPC but sheet M0.0 calls out the IPC.)
2. Revise sheet M3.1; the background is printed so faintly that it is not legible. Reference: Section 103.2.3, UPC 2006.
3. Provide a floor drain in the Men's restroom and in Toilet 2. Reference: Section 411.2, UPC 2006.
4. Show that the floor of the Men's restroom and the floor of Toilet 2 slope toward the required floor drains. Reference: Section 411.2, UPC 2006.
5. Clarify why the specified drinking fountains do not meet the accessibility requirements as shown in Section 1109.5, IBC 2006.
6. Provide wall and flooring material in the restrooms and in Toilet 1 and Toilet 2 that meets the requirements of Section 1210, IBC 2006.
7. Sheet M3.1 shows a 4" GCO at the north end of the building drain but a 3" building drain extending south from the cleanout. Coordinate the specified sizes per Sections 311.5 and 707.11, UPC 2006.
8. Provide a vent downstream of the backwater valve to provide ventilation of the building sewer per Section 904.1, UPC 2006.
9. Revise the size of the provided scuppers to comply with the requirements of Section 1101.11.2.1, UPC 2006.
10. Show how the roof is to be provided with overflow protection. Reference: Section 1101.11.2, UPC 2006.
11. Provide calculations to show that the size of the overflow in the roof drain collector box has a drainage capacity equal to that of the scupper. Reference: Section 1101.11.2.2.1, UPC 2006.
09/13/2010 ROBERT SHERRY WATER REVIEW Denied Clarify the size of the water meter serving the site; the civil drawing (sheet 2 of 4) shows a 2" water meter but the water calculation on sheet M8.1 shows a 1-1/2" water meter. Reference: Section 103.2.3, UPC 2006.
09/14/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise sheets M1.1 and M1.2; the background is printed so faintly on both sheets that it is not legible. Reference: Section 106.3.1, IMC 2006.
2. Provide sufficient detail on the drawings to evaluate the energy compliance calculations for the building envelope. The information shall, as a minimum, include the construction of the windows and the assembly U-factors for the windows along with the SHGC for the glazing. Reference: Section 104.2, IECC 2006.
3. Provide information on the sequence of operation for the restroom exhaust fans to show that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006.
4. Ventilation calculations are based on the net floor area; there are no "offsets" included in the IMC. Revise the ventilation calculations appropriately. Reference: Sections 106.3.1 and 403.3, IMC 2006 and footnote a, Table 403.3, IMC 2006.
09/24/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10CM02365
5910 E 5 th #2
Education Bldg

The electrical plans have been denied for the following:

1. Sheet E2.2, Circuit P2A-18 used for receptacles marked spare in panel schedule.
2. Sheet E2.2, Circuit P2A-11 used for receptacles in restrooms, listed as lighting control in panel schedule.
3. Sheet E2.2, Circuits P2A- 10,12,14 used for receptacles marked as spares in panel schedule.
4. Sheet E5.1, Panel P2A--- total va for phase B incorrect.
5. Need to provide darker background for plans, cannot be clearly identified.

Ray T Majuta, Elect Pln Ck,
PDSD, City of Tucson
9/26/10
Ray.Majuta@tucsonaz.gov
09/28/2010 GERRY KOZIOL WWM REVIEW Denied need to have location & method of connection review by Kurt Stemm- 3rd floor- 740-6607
need WW credit evaluation 5th floor. waste water maps & records and /or pay any outstanding WW fees if applicable

Final Status

Task End Date Reviewer's Name Type of Review Description
10/04/2010 CPIERCE1 OUT TO CUSTOMER Completed
10/04/2010 SUE REEVES REJECT SHELF Completed