Permit Number: T10CM02361
Parcel: 137055220

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM02361
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/08/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/08/2010 ERIC NEWCOMB ZONING HC REVIEW Approved
09/08/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
09/08/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project T10CM02361


Electrical pland denied for following:

1.Power plan shows some circuits on panel B, only panel A shown on this plan ?
2. Panel A has several circuits not show on lighting or power plan such as A-19 thur 27 ? Please show them as spares or on plan.
3.Circuit A-30 is shown on panel as spare ?
4.Circuit A-17 shows as a spare.


Ray T Majuta
PDSD, City of Tucson
9/8/10
Ray.Majuta@tucsonaz.gov
09/08/2010 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.