| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/08/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/08/2010 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved | |
| 09/08/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 09/08/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project T10CM02361 Electrical pland denied for following: 1.Power plan shows some circuits on panel B, only panel A shown on this plan ? 2. Panel A has several circuits not show on lighting or power plan such as A-19 thur 27 ? Please show them as spares or on plan. 3.Circuit A-30 is shown on panel as spare ? 4.Circuit A-17 shows as a spare. Ray T Majuta PDSD, City of Tucson 9/8/10 Ray.Majuta@tucsonaz.gov |
| 09/08/2010 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |