Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T10CM02361
Parcel: 137055220

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM02361
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/26/2010 TERRY STEVENS ZONING REVIEW Approved
08/26/2010 BIANCA RAMIREZ ENGINEERING REVIEW Approved
08/26/2010 ERIC NEWCOMB ADA REVIEW Passed
08/26/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A-2; FLOOR PLAN: A MINIMUM OF TWO RESTROOMS ARE REQUIRED FOR THE OCCUPANT LOAD PROVIDED. VERIFY.
2. SHEET A-2; FLOOR PLAN: ACCESS TO THE EXIT BY THE OFFICE IS NOT ACCEPTABLE PER IBC SECTION 1014. REARRANGE THE RESTROOM/FITTING AREA/OFFICE/ DRINKING FOUNTAIN GROUPING TO MEET CODE REQUIREMENTS..
3. SHEET A-2; FLOOR PLAN: THE TWO DOORS OPENING INTO THE HALL (FROM THE TOILET AND FITTING AREA) REDUCE THE HALL TO AN UNACCEPTABLE WIDTH. REVISE THIS CONDITION.
08/26/2010 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENTS.
08/26/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/27/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/27/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied
08/27/2010 ROBERT SHERRY WATER REVIEW Approved
08/27/2010 DAVE MANN FIRE REVIEW Approv-Cond Swap doors 2 and 3 to swing in oposite direction, see building comment.
08/27/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide an appeal to the building official if the IPC is to be used in lieu of the UPC.
2. Provide a complete plumbing plan, including a plan view of the water, waste, and vent piping. Coordinate the riser diagram with the fixture arrangement.
3. Provide specifications of the plumbing fixtures and appliances being installed.
4. Provide a detail of the water heater installation, including valves, T&P relief piping, expansion tank, and vacuum relief.
5. If the water heater is to be mounted on a platform, show how the platform is to be constructed an how it is to be connected to the building structure.
6. Show how the temperature of the hot water to the lavatory is to be limited to a maximum temperature of 110 degrees Fahrenheit.
09/07/2010 CPIERCE1 WWM REVIEW Needs Review