Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project : T10CM02360

1. Circuit l-17 not on plan.
2. Circuit L-38 is used for water heater (120 volts) and also receptacles.
3. Circuit L-4 is used for receptacles and lights and is on a Time Clock.
4. Panel H has a Water Heater on it so doew Panel L ?
5. Show the circuits for VAV on plan.
6. Panel H shows Circuit for VAV 1 at 277 volts while Circuit 8,10,12 for VAV 2 is shown at 480 volts 3 phase
7. How will lighting be switched ?


Ray T Majuta,
PDSD, City of Tucson
Elect Pln CK
9/15/10