Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T10CM02360
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM02360
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/26/2010 TERRY STEVENS ZONING REVIEW Approved
08/26/2010 BIANCA RAMIREZ ENGINEERING REVIEW Approved
08/27/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Electrical denied for following:
1. Provide 2006 IECC Light Budget Calc's
2. Provide load in watts or va per circuit per phase
3.Provide location of panels,transformer on plan
4. provide location of landlords SES on plan

Ray T Majuta
PDSD City of Tuc
Elect Plan CK
8/27/10
520-837-4988
08/27/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/27/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A-11; STUD SCHEDULE: NOTE 2 REFERENCES A DETAIL 15/A9 FOR BRACING REQUIREMENTS OF THE PARTITION WALLS. PROVIDE A DETAIL.
2. SHEET A-11; WALLS 6 AND 7: PROVIDE STRUCTURAL CALCULATIONS FOR THE MEZZANINE ABOVE THE RESTROOM. INCLUDE ON THE DRAWINGS MEMBER SIZES.
08/27/2010 ROBERT SHERRY WATER REVIEW Approved
08/27/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide an appeal to the building official if the IPC is to be used in lieu of the UPC.
2. Coordinate the riser diagram with the fixture arrangement.
3. Show how the temperature of the hot water to the lavatory is to be limited to a maximum temperature of 110 degrees Fahrenheit.
08/27/2010 DAVE MANN FIRE REVIEW Approved
08/27/2010 ERIC NEWCOMB ADA REVIEW Passed
08/27/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/27/2010 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENTS.
09/07/2010 CPIERCE1 WWM REVIEW Needs Review