Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T10CM02325
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/02/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Coordinate the grease interceptor calculation with the fixtures being installed in the restaurant. Sizing shall be done using Section 1014.3.6.1, UPC 2006. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/04/2010 | CPIERCE1 | OUT TO CUSTOMER | Completed |