Permit Number: T10CM02310
Parcel: 113061030

Address:
1328 E LIND RD

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T10CM02310
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/25/2010 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS T10CM02310
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2005 National Electrical Code and Arizona Revised Statutes. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

GENERAL NOTES:
" Provide two copies of plans for approval.

STRUCTURAL PLANS:
1. The roof structure may not be suitable for additional dead loading without modification. Clarify if the 2 x 8 rafters are spanning a building structure with 14 feet between bearing walls, or if the roof is an open porch. In this case show the span between load bearing wall and beam. Provide a design for supporting the required 15 PSF dead load along with a 20 PSF live load.
DIAGRAMS / CALCULATIONS
1. Show a DC grounding electrode conductor size equal to the DC supply conductors and not smaller than #8 (copper), NEC 250.166 (B) & 690.47(C)(2). Show this conductor size between the inverter and the service ground.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/01/2010 CINDY AGUILAR OUT TO CUSTOMER Completed
09/01/2010 SUE REEVES REJECT SHELF Completed