Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM02305
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/20/2010 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 08/20/2010 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 08/20/2010 | DAVE MANN | FIRE | REVIEW | Approved | |
| 08/23/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 08/23/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/23/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/23/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | Tentant is doubleing his square footage. Need new C of O and need up dated building code review check list. |
| 08/23/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Revise waste piping for the service sink. A waste pipe may not drain into a vent. Reference: Section 311.4, UPC 2006. |
| 08/23/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/23/2010 | RONALD BROWN | ADA | REVIEW | Passed | |
| 08/23/2010 | RONALD BROWN | ZONING HC | REVIEW | Denied | Reference building folder comments |
| 08/24/2010 | CPIERCE1 | WWM | REVIEW | Needs Review | . |