Permit Number: T10CM02263
Parcel: 114512070

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM02263
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/20/2010 DAVE MANN FIRE REVIEW Denied Two exits required. One of the exits depicted on plan passes through storage area. Per 2006 IBC, egress shall not pass through storage rooms(section 1014.2). See exceptions in same section for methods to alleviate this situation.
09/01/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A2.1 (FLOOR PLAN); SHEET A5.1 (PLAN 6): THE PLANS INDICATE A SINGLE DRINKING FOUNTAIN. REVISE.
2. SHEET A2.2; DETAIL 1: PROVIDE THE BRACING SIZE AND SPECIFIC CONNECTION TO THE TOP OF THE WALL AND TO THE BLOCKING ABOVE. PROVIDE THE BLOCKING SIZE AND SPECIFIC CONNECTION TO THE EXISTING STRUCTURE MEMBERS.
3. SHEET A5.1; DETAILS 4 AND 5: LETTERING MUST BE A MINIMUM OF 3/32" IN HEIGHT PER CITY OF TUCSON STANDARDS. REVISE.
4. SHEET A5.1; DETAIL 5 (AT DRINKING FOUNTAIN): REVISE ALL REFERENCES TO ADAAG.
5. SHEET A5.1; ELEVATION 15: PROVIDE DIMENSIONS INDICATING THE SINK/COUNTER ARE ACCESSIBLE AS REQUIRED BY THE 2006 IBC, SECTION 1109.
6. SHEET A6.1; DETAILS SK2 AND SK3: LETTERING MUST BE A MINIMUM OF 3/32" IN HEIGHT PER CITY OF TUCSON STANDARDS. REVISE.
7. SHEET A6.1; DETAIL SK2: THE BEAM DEPICTED IN DETAIL X REFERENCES THE BEAM PER PLAN. THE BEAM WAS NOT LOCATED ON A PLAN. CLARIFY THE SIZE.
8. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
09/02/2010 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENTS.
09/02/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference: Sections 310.0 and 314.5, UPC 2006.
2. The specified drinking fountain does not meet the accessibility requirements as shown in Section 1109.5, IBC 2006.
09/02/2010 ROBERT SHERRY WATER REVIEW Approved
09/02/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
09/02/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/14/2010 GERARDO BONILLA OUT TO CUSTOMER Completed