Permit Number: T10CM02261
Parcel: 12510006C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM02261
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/25/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The records for the City of Tucson indicate that the Target store at 3699 E Broadway Blvd. was approved with ventilation per the 2000 IMC but not with an engineered ventilation system. Clarify the amount of outside being supplied to the building by the replacement for RTU-9, DHU-1.
10/25/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not resolved; General Note E/P351 addresses the issue but detail 5/PM02 is still incorrect. Provide upper terminal cleanouts on horizontal drainage pipe over 5 feet in length (e.g. the floor drain by the water heater in room 184). Reference: Section 707.4, UPC 2006.
2. Comment not resolved; General Note F/P351 addresses the issue but detail 5/PM02 is still incorrect. Provide cleanouts sized per Section 707.11, UPC 2006 (e.g. the 2" waste for the hand sink transitioning to a 4" waste).
11/09/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
11/09/2010 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/18/2010 GERARDO BONILLA OUT TO CUSTOMER Completed
11/18/2010 SUE REEVES REJECT SHELF Completed