Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T10CM02261
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/25/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | The records for the City of Tucson indicate that the Target store at 3699 E Broadway Blvd. was approved with ventilation per the 2000 IMC but not with an engineered ventilation system. Clarify the amount of outside being supplied to the building by the replacement for RTU-9, DHU-1. |
| 10/25/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not resolved; General Note E/P351 addresses the issue but detail 5/PM02 is still incorrect. Provide upper terminal cleanouts on horizontal drainage pipe over 5 feet in length (e.g. the floor drain by the water heater in room 184). Reference: Section 707.4, UPC 2006. 2. Comment not resolved; General Note F/P351 addresses the issue but detail 5/PM02 is still incorrect. Provide cleanouts sized per Section 707.11, UPC 2006 (e.g. the 2" waste for the hand sink transitioning to a 4" waste). |
| 11/09/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 11/09/2010 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/18/2010 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 11/18/2010 | SUE REEVES | REJECT SHELF | Completed |