Permit Number: T10CM02261
Parcel: 12510006C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM02261
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/18/2010 MARTIN BROWN FIRE REVIEW Approved
08/27/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved 1. SHEET A011; DETAIL 2: REMOVE THE ADAAG REFERENCE IN THE TITLE. THIS PROJECT FALLS UNDER THE 2006 IBC AND ICC/ANSI A117.1-2003.
2. SHEET A011: STAMP AND SIGN THIS SHEET.
08/30/2010 ROBERT SHERRY WATER REVIEW Approved
08/30/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide upper terminal cleanouts on horizontal drainage pipe over 5 feet in length (e.g. the floor drain by the water heater in room 184). Reference: Section 707.4, UPC 2006.
2. Provide cleanouts sized per Section 707.11, UPC 2006 (e.g. the 2" waste for the hand sink transitioning to a 4" waste).
08/30/2010 ERIC NEWCOMB ZONING HC REVIEW Approved
08/30/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Clarify the amount of outside air being supplied to the building by the replacement for RTU-9, DHU-1. (Note that the elevation of the building roof is approximately 2556 feet, not 2661 feet) Reference: Section 403.3, IMC 2006.
09/15/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10CM02261
3699 E Broadway
Target TI

Electrical plans denied for following:

1. All submitted material and information on plans to be minimum text size 3/32" per Administrative requirements.
2. Sheet E 401, indicate circuit supplying equipment at homerun arrows, rather that having to chase down at panel schedule. (Panels LP12-B and LP 13.)
3. Panel 13 is not shown on one line diagram, also show location for panel on plan.
4. Indicate a date information was obtained for Utility Metered Load and insert date inside box where this load is shown. on Sheet E001.

Ray T Majuta,
PDSD, City of Tucson,
Elect Pln Ck,
9/16/10
Ray.majuta@tucsonaz.gov
09/16/2010 GERRY KOZIOL WWM REVIEW Denied NEED TO PROVIDE PLUMBING FIXTURE SCHEDULE LISTING ADDED
REMOVE WASTE CONNECTED FIXTURES WITH WASTE LINE SIZES & DIRECT, INDIRECT CONNECTIONS

Final Status

Task End Date Reviewer's Name Type of Review Description
09/28/2010 DELMA ROBEY OUT TO CUSTOMER Completed
09/28/2010 SUE REEVES REJECT SHELF Completed