Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM02261
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/18/2010 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 08/27/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | 1. SHEET A011; DETAIL 2: REMOVE THE ADAAG REFERENCE IN THE TITLE. THIS PROJECT FALLS UNDER THE 2006 IBC AND ICC/ANSI A117.1-2003. 2. SHEET A011: STAMP AND SIGN THIS SHEET. |
| 08/30/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/30/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide upper terminal cleanouts on horizontal drainage pipe over 5 feet in length (e.g. the floor drain by the water heater in room 184). Reference: Section 707.4, UPC 2006. 2. Provide cleanouts sized per Section 707.11, UPC 2006 (e.g. the 2" waste for the hand sink transitioning to a 4" waste). |
| 08/30/2010 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved | |
| 08/30/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Clarify the amount of outside air being supplied to the building by the replacement for RTU-9, DHU-1. (Note that the elevation of the building roof is approximately 2556 feet, not 2661 feet) Reference: Section 403.3, IMC 2006. |
| 09/15/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T10CM02261 3699 E Broadway Target TI Electrical plans denied for following: 1. All submitted material and information on plans to be minimum text size 3/32" per Administrative requirements. 2. Sheet E 401, indicate circuit supplying equipment at homerun arrows, rather that having to chase down at panel schedule. (Panels LP12-B and LP 13.) 3. Panel 13 is not shown on one line diagram, also show location for panel on plan. 4. Indicate a date information was obtained for Utility Metered Load and insert date inside box where this load is shown. on Sheet E001. Ray T Majuta, PDSD, City of Tucson, Elect Pln Ck, 9/16/10 Ray.majuta@tucsonaz.gov |
| 09/16/2010 | GERRY KOZIOL | WWM | REVIEW | Denied | NEED TO PROVIDE PLUMBING FIXTURE SCHEDULE LISTING ADDED REMOVE WASTE CONNECTED FIXTURES WITH WASTE LINE SIZES & DIRECT, INDIRECT CONNECTIONS |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/28/2010 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 09/28/2010 | SUE REEVES | REJECT SHELF | Completed |