Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Active
Review Details: COMMERCIAL TI
Permit Number - T10CM02260
Review Name: COMMERCIAL TI
Review Status: Active
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/17/2010 | ANY | PLUMBING-COMMERCIAL | REVIEW | Active | |
08/17/2010 | ANY | MECHANICAL-COMMERCIAL | REVIEW | Active | |
08/17/2010 | ANY | WATER | REVIEW | Active | |
08/17/2010 | ANY | WWM | REVIEW | Active | |
09/17/2010 | DAVID RIVERA | ZONING | REVIEW | Approved | |
09/17/2010 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
10/01/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | Project: T10cm02260 5118 S 12TH The electrical plans have been denied for the following: 1. The service riser is customer installed, show size of conduit and conductors. 2. The 4 # 500 mcm conductors are required to carry an equipment ground sized per 250.66, which needs to be 1/0 cu. 3. The ground system for the upgraded service is required to have a water and gas bond, please show. 4. The grounding system shown for the existing service now will be moved to the new service, either show disconnection to neutral or eliminate. Ray T Majuta, PDSD, City of Tucson, Elect Plan CK, 10/1/10 Ray.Majuta@tucsonaz.gov |
10/01/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
10/01/2010 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved | |
10/01/2010 | DAVE MANN | FIRE | REVIEW | Approved | |
10/01/2010 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
10/01/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |