Permit Number: T10CM02233
Parcel: 11615088L

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM02233
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/20/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The minimum insulation for ducts located in indirectly conditioned spaces within the building envelope is R-4.2 (installed). Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson.
2. Provide auxiliary drain pans or secondary drain systems for the new water-source heat pump units. Reference: Section 307.2.3 IMC 2006.
08/20/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The maximum length of the horizontal section of a vent may not exceed one-third of the total allowable vent length noted in Table 7-5, UPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/25/2010 DELMA ROBEY OUT TO CUSTOMER Completed
08/25/2010 SUE REEVES REJECT SHELF Completed