Permit Number: T10CM02232
Parcel: 11615088L

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T10CM02232
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/20/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
09/20/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show how the discharge duct of the booster fan terminates at the building wall and explain how the enclosure of the 4" exhaust duct within a 6" duct prevents contamination of the return air plenum. Reference: Section 601.4, IMC 2006.
09/20/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved