Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T10CM02232
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/20/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
09/20/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show how the discharge duct of the booster fan terminates at the building wall and explain how the enclosure of the 4" exhaust duct within a 6" duct prevents contamination of the return air plenum. Reference: Section 601.4, IMC 2006. |
09/20/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved |