Permit Number: T10CM02221
Parcel: 140280340

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T10CM02221
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/20/2011 RONALD BROWN HC SITE REVIEW Denied APPLICANT'S RESPONSE TO THE RESUBMITTAL COMMENTS IS CONSIDERED "NON-RESPONSIVE". PLEASE RESPOND IN WRITING TOI ALL THE COMMENTS LISTED BELOW WHICH ARE A COPY OF THE RESUBMITTAL COMMENTS.

1. OK
2. OK
3. Please provide spot grades throught the NEW CONCRETE PEDESTRIAN accessible route showing compliance with 2006 IBC, ICC (ANSI 117.1), Section 403.3
PLEASE COMPLY WITH MODIFIED COMMENT.

4. OK


5. BECAUSE YOU HAVE CHANGED THE ACCESSIBLE PARKING LAYOUT, Please provide a large scale detail of the accessible parking including the following:
THE LARGE SCALE DETAIL ON SHEET A1 IS NOT THE SAME AS DESIGNED ON SHEET 1-SITE PLAN. PLEASE SHOW EXACT ACCESSIBLE PARKING LAYOUT AND INCLUDE ALL CODE COMPLIANCE REQUIREMENTS AS PER 1BC CHAPTER 11 AND ICC-ANSI 117.1, SECTION 502 AND 406.
SHOW ALL RAMPS REQUIRED AND EVERYTHING LISTED BELOW:
a. Grades slopes as per ICC (ANSI 117.1), Section 502.5
b. Sizes of all parking spaces and aisles including dimensions for all spaces including "Van Accessible"
c. Provide 1 "Van Accessible space as per section 1106.5
d. Signage
e. All required accessible parking aisles
f. Access to the accessible route in either flush condition or with a curb/sidewalk ramp as per Sections 405 and /or 406.

6. OK

7. Please provide large scale details of the NEW EXITS PROVIDED, PATIO exit, KITCHEN EXIT and the concrete walk condition at THOSE exits showing compliance with Section 404 and 303.
PLEASE RESPOND TO MODIFIED COMMENT

8. OK

9. PLEASE PROVIDE ALL RESPONSES IN WRITING.

END OF REVIEW
10/24/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed