Review Details: POST 3RD PARTY REVIEW

Permit Number - T10CM02196
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/08/2010 ROBERT SHERRY WATER REVIEW Approved
11/08/2010 MARTIN BROWN FIRE REVIEW Denied Fire sprinklers are required. Add note to plan indicating sprinklers will be installed.

Please include the following fire sprinkler design criteria to the plans.
1. Flow data (static pressure, residual pressure, GPM)
Available from the Fire Department (520) 837-7029 or 837-7030.
2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D)
3. The hazard classification of the building, including any special hazards.
4. The density required of the water supply.

IFC 907.2.1
Fire alarm system is needed.

Please show existing fire hydrants with dimensions to property lines on site plan. See C.O.T. amendments to 2006 IFC (Section 508.5.1) for spacing requirements.
11/09/2010 JASON GREEN ENGINEERING REVIEW Approved
11/15/2010 STEVE SHIELDS ZONING REVIEW Approved
11/16/2010 GERRY KOZIOL WWM REVIEW Approved
11/17/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
11/17/2010 CPIERCE1 OUT TO CUSTOMER Completed