Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T10CM02196
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/08/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/08/2010 | MARTIN BROWN | FIRE | REVIEW | Denied | Fire sprinklers are required. Add note to plan indicating sprinklers will be installed. Please include the following fire sprinkler design criteria to the plans. 1. Flow data (static pressure, residual pressure, GPM) Available from the Fire Department (520) 837-7029 or 837-7030. 2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D) 3. The hazard classification of the building, including any special hazards. 4. The density required of the water supply. IFC 907.2.1 Fire alarm system is needed. Please show existing fire hydrants with dimensions to property lines on site plan. See C.O.T. amendments to 2006 IFC (Section 508.5.1) for spacing requirements. |
| 11/09/2010 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 11/15/2010 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 11/16/2010 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 11/17/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/17/2010 | CPIERCE1 | OUT TO CUSTOMER | Completed |