Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T10CM02188
Parcel: 13314236C

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL

Permit Number - T10CM02188
Review Name: 3RD PARTY REVIEW-COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/09/2010 CPIERCE1 WWM REVIEW Needs Review
08/09/2010 CPIERCE1 ZONING REVIEW Needs Review
08/09/2010 CPIERCE1 FIRE REVIEW Needs Review
08/09/2010 CPIERCE1 WATER REVIEW Needs Review
08/09/2010 CPIERCE1 ENGINEERING REVIEW Needs Review
08/09/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
08/09/2010 CPIERCE1 ZONING HC REVIEW Needs Review
08/12/2010 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Approved
08/12/2010 STANTEC 3RD PARTY REVIEW-COMMERCIAL AT 3RD PARTY OFFICE Completed