Permit Number: T10CM02185
Parcel: 14117690C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM02185
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/23/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Detail 3/P1 shows heat traps that are not integral to the water heater ("at the contractor's discretion"). If the specified water heater is not supplied with integral heat traps, provide 0.5" of insulation with a maximum conductivity of 0.27 BTU per inch/H F on the first 8 feet of supply and discharge piping. Reference: Section 504.5, IECC 2006.
2. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves (e.g. automatic clothes washer). Reference: Section 609.10, UPC 2006.
08/23/2010 ROBERT SHERRY WATER REVIEW Approved
08/23/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show how the fan coils are being connected to the building structure. Reference: Section 302.1, IMC 2006.
2. The submitted calculations indicate that both fan coil units are to receive outside air but it is unclear how they will receive it. Show the outside air ducts. Reference: Section 106.3.1, IMC 2006.
09/02/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
09/10/2010 STEVE SHIELDS ZONING REVIEW Approved