Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/23/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Detail 3/P1 shows heat traps that are not integral to the water heater ("at the contractor's discretion"). If the specified water heater is not supplied with integral heat traps, provide 0.5" of insulation with a maximum conductivity of 0.27 BTU per inch/H F on the first 8 feet of supply and discharge piping. Reference: Section 504.5, IECC 2006. 2. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves (e.g. automatic clothes washer). Reference: Section 609.10, UPC 2006. |
08/23/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
08/23/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show how the fan coils are being connected to the building structure. Reference: Section 302.1, IMC 2006. 2. The submitted calculations indicate that both fan coil units are to receive outside air but it is unclear how they will receive it. Show the outside air ducts. Reference: Section 106.3.1, IMC 2006. |
09/02/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
09/10/2010 | STEVE SHIELDS | ZONING | REVIEW | Approved |