Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM02160
Parcel: 126211130

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T10CM02160
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/06/2010 MARTIN BROWN FIRE REVIEW Denied This residence will have a "fire calculation area"(2006 IFC Appendix B, Section B104.1) greater than 3,600 sq. ft.: therefore this house will require a residential sprinkler system unless the fire flow in the nearest hydrant is a minimum of 2500 GPM (2006 IRC Appendix L, as amended and 2006 IFC Appendix B, Table B104.1, assuming type V-B construction). Call David Mann (837-7029) or Martin Brown(837-7030) for fire flow information. Residential or quick response sprinklers shall be used. The sprinkler system may be connected to the domestic water supply, provided the required design density can be met. Be advised that Tucson Water will not allow a residential sprinkler system to be supplied by a 5/8" meter. A 1" meter will be required by Tucson Water. Residential fire sprinkler system shall be installed in accordance with the 2006 IFC and NFPA 13D.
08/12/2010 GERRY KOZIOL WWM REVIEW Denied need credit evaluation
need capcity evaluation-3rd floor, Kurt Stemm-740-7706
08/30/2010 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS T10CM02160

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
Show corrections and revisions on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and notate sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

The City of Tucson adopted the 2006 IRC with amendments on 6/12/2007 and the 2006 UPC with amendments on 7/10/2007. For initial construction: Effective 1/1/2007 the Inclusive Home Design; starting 3/1/2009 Solar Water Preparation and 7/1/2009 Solar Photo-Voltaic Preparation are required for all new SFR and duplex plans. Show the code references on the plans. Amendments to adopted codes are at the City web-site http://www.tucsonaz.gov: Planning, Building, & Business; under the Building topic; Building Ordinances and Codes; Building Codes

GENERAL NOTES:

" Provide ¼" = 1' scaled drawings with legible notation (minimum 3/32" lettering).
" Remove the "optional" reference for the Garage on sheet #1. The site plan may include future structures, but the plans may only include existing and proposed for construction structures. The submitted plans currently include a Garage for permitted construction.

FOUNDATION PLANS:

1. Show compliance with termite treatment, R320 as amended.
2. Specify all anchor-bolts with 7" embedment into concrete or masonry, R319.1 & R403.1.6.
3. Show Alternate Braced Wall Panel device location and installation method for providing the required 1800 LBS uplift capacity, R602.10.6. The (type 1) PAHD42 is undersized.

FLOOR PLANS:

1. Show window and door sizes on the Floor Plan, R106.1.1. Add appropriate symbols from the schedules at each opening.
2. Show compliance with R303.1 providing 8% natural light 4% natural ventilation into the Data room.
3. Show compliance with R304 providing habitable rooms with not less than 70SF. The Data Room is undersized.
4. Show the door from a garage to dwelling with a 20-minute fire rating (or 1-3/8" solid core) with self-closing and self-latching provision, 2006 IRC Amendment section 309.1.
5. Show compliance with R310 providing egress from Bedroom #1.
6. Show the location of a minimum 22" x 30" attic access. Attic access is required if the space exceeds 30 SQ FT with a minimum of 30" of headroom and located in a hallway or readily accessible space, R807.1, or show passage between the proposed and accessible existing and attic areas.

STRUCTURAL PLANS:

1. Show the location of shear wall symbols on the floor plan, R301.1.
2. Provide existing roof framing sizes and spans between load bearing walls for supporting the added rooftop HVAC load. Engineered trusses may require an engineer analysis for verifying the load carrying capacity for the additional load, M1401.
3. Provide detail for bracing trusses at gable ends to prevent rotation and provide lateral stability, R802.10.3.
4. Notate scissor truss installation with (TC) slotted ties at one wall connection providing appropriate uplift rating per engineered design, R802.10.5.

SECTIONS - DETAILS:

1. The plans are mislabeled with ¼" scale, R106.1.1. Provide actual ¼" scale plans.
2. Show detail and section references on the Floor Plan, R106.1.1. Each detail appearing on sheet #4 should be referenced for location on a plan.
3. Show the location of roof drainage components associated with the parapet detail, R106.1.1. Add crickets and scuppers on a plan view.
4. Revise the "water resistant" notation sheet #3 to show fiber-cement board or glass mat gypsum backers for tiled walls in tub and shower areas, R702.4.2.
5. Specify water-resistive barrier equivalent to two layers of Grade D paper over the wood based sheathing of exterior plaster wall coverings, R703.6.3.
6. Clarify the placement of ceiling/roof insulation for determining the need for attic ventilation, R806.
7. Calculate the attic ventilation using 1 to 150 of attic area in compliance with R806.2. Provide appropriate upper and lower space vents when applying the reduced area calculation. Account for the existing attic space if removing or blocking existing vents.
8. Notate all roof slopes appropriate with selected material, R901.1.

PLUMBING PLANS:

1. Provide water hammer arresters wherever quick-closing valves are installed in a water distribution system. The devices should conform to ASSE 1010-2004. Water hammer arresters are required for clothes washer, dishwasher and refrigerator water connections, UPC 609.10.
2. Provide a revised fixture unit schedule using 2006 code values for determining required service pipe diameter, UPC 610.8, Table 6-6. Those shown are not consistent with current codes. The existing water service pipe and meter require replacement to larger sizes, UPC 610.8, Table 6-6.
3. Show a clean out at the proposed kitchen sink area UPC 707.4 W/ State amendment.

MECHANICAL PLANS:

1. Provide heating facilities in all habitable rooms, R303.8.
2. Show supply and return ducts with minimum R-8 insulation (includes vented attics) except when completely located inside the thermal envelope, R1103.2.1.
3. Provide an equipment specification list including the furnace size and cooler tonnage capacity, M1302.1.
4. Show dryer vent size and location for venting to exterior, M1501.
5. Show bathroom exhaust fan locations for venting to exterior with minimum 50 CFM rating R303.3 and M1507.3.
6. Provide return air duct and register sizes meeting minimum requirements of 72 SQ IN/ ton, M1602. Minimum duct/register size: heat pump or air conditioner - 6 SQ IN per 1,000 BTU, M1403.1 (1 ton cooling = 12,000 BTU).

ELECTRICAL PLANS:

1. Provide an Electrical Plan consistent with the Floor Plan, R106.1.1. Include the Foyer, Extended Living and Data Rooms.
2. Show locations of smoke alarm, R313. Notate that all smoke alarms must be interconnected with a power source from the building wiring, and be equipped with battery backup. Smoke alarms are required outside each separate sleeping area, R313.2.
3. Interior alterations require the installation of smoke alarms at existing bedrooms, R313.2.1. Provide notation if existing or proposed.
4. Provide an electrical riser diagram service size consistent with the plan (400A), E3303.
5. Provide an electrical load calculation with a SQ. FT. size consistent with the floor plan, E3502.2. Also, show all connected appliances (4 water heaters, 2 ranges, etc.)
6. Designate the circuit number at the location of each light fixture, receptacle, appliance and equipment disconnect switch, E3603.5.
7. Provide a feeder load calculation for any sub-panels, E3604.2.
8. Show receptacle outlets at each kitchen counter space wider than 12" with no point along the wall line more than 24" from a receptacle outlet, E3801.4.1.
9. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, E3603.2 and E3801.3 through E3801.4.5.
10. Show a receptacle outlet within 3' of each lavatory basin in each bathroom, E3801.6. Show Bathroom receptacles on a separate 20 AMP circuit (dedicated) with outlets at no other locations, E3603.4.
11. Provide an exterior outlet at grade level located at both the front and back of the dwelling, E3801.7. These outlets require GFCI protected E3802.3.
12. Show or notate a disconnect means or a locking breaker for the water heater, E4001.5.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Tucson is in climate zone 2B. The simplified prescribed energy values for glazing and skylights is U=0.75, ceiling R=30 and walls R=13. Show the "R" values of insulation and the maximum "U" factors of the windows and doors on the plans, N1101.2.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/07/2011 GERARDO BONILLA OUT TO CUSTOMER Completed
01/07/2011 GERARDO BONILLA REJECT SHELF Completed