Permit Number: T10CM02159
Parcel: 11205060C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM02159
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/05/2010 RONALD BROWN ADA REVIEW Passed
08/06/2010 MARTIN BROWN FIRE REVIEW Denied Address on plans does not match address on permit form.
Indicate if building is sprinklered.
Occupant load is calculated at 1 per 60 sq. ft. This is the number for 2nd floor Mercantile occupancy. Ground floor ratio is 1 per 30 sq. ft. Another exit may be required.
08/11/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A1; TENANT IMPROVEMENT CODE REVIEW (OCCUPANT LOAD): VERIFY THE MAXIMUM FLOOR AREA ALLOWABLE PER OCCUPANT (TABLE 1004.1.1 OF THE 2006 IBC). 30 SF/OCCUPANT IS TYPICAL FOR MERCANTILE. REVISE EXIT REQUIREMENTS AS REQUIRED.
2. SHEET A1; FLOOR PLAN: PROVIDE AN ENLARGED, DIMENSIONED PLAN OF THE WOMEN'S AND MEN'S RESTROOMS, INDICATING ACCESSIBILITY REQUIREMENTS OF ICC/ANSI A117.1-2003 (CHAPTER 6) ARE MET.
3. SHEET A1; FLOOR PLAN: PROVIDE AN ELEVATION OF THE CASH WRAP COUNTER, INDICATING ACCESSIBILITY REQUIREMENTS OF ICC/ANSI (SECTION 904) ARE MET.
4. SHEET A1; CODE REVIEW (NUMBER OF EXITS): THE DRAWING INDICATES I EXIT IS PROVIDED, WHILE THE FLOOR PLAN INDICATES 2. CLARIFY.
5. SHEET A1; FLOOR PLAN: IF TWO EXITS ARE REQUIRED, VERIFY THE DOORWAY ARRANGEMENT MEETS IBC SECTION 1015.2.1, AND SHOW THESE DIMENSIONS ON THE DRAWINGS.
6. SHEET S1.0; REFERENCE PLAN: PROVIDE STRUCTURAL CALCULATIONS FOR THE STEEL AROUND THE NEW MASONRY OPENING.
7. SHEET S1.0; DETAIL 101: THE BASE PLATE WIDTH MATCHES THE COLUMN WIDTH. IS IT POSSIBLE TO WELD ALL AROUND THE COLUMN WITH A 3/16" FILLET WELD? VERIFY.
8. SHEET S1.0; DETAIL 101: THE TUBE COLUMN IS REFERENCED AS A HSS6X4X1/4. INDICATE THE CORRECT SIZE ON THE SECTION CUT #. THE BASE PLATE AND EXPANSION ANCHORS WILL NOT WORK AS SHOWN. REVISE.
9. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
08/12/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/12/2010 ERIC NEWCOMB ZONING HC REVIEW Denied
08/20/2010 ROBERT SHERRY WATER REVIEW Denied Tucson Water limits a 1" meter to a maximum demand of 25 GPM. Provide a letter from Tucson Water confirming that the use of a 1" water meter will be allowed for this project with a demand of 29 GPM. Reference: Sections 610.2 and 610.12, UPC 2006
08/20/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
08/20/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Clarify the scope of the mechanical work for this activity. The "New Mechanical General Notes" on sheet A1 indicate that two new 5-ton split-system heat pumps and new ductwork are being installed but the mechanical drawing, MP-1, only shows two exhaust fans being installed.
08/31/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Electrical plans denied for followiing:

1. No electrical plans provided for new 5 ton mechanical units to be added per sheet A. No electrical plans for 15 new 2 x4 to be installed as per sheet A1. No electrical plans for new ex-haust fans for toilets.

Ray T Majuta
Elect Plans Ex
PDSD City of Tuc,
8/31/10
Ray.Majuta@tucsonaz.gov
09/02/2010 DROBEY1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/02/2010 DELMA ROBEY OUT TO CUSTOMER Completed