Permit Number: T10CM02138
Parcel: 13403037B

Address:
8727 E 22ND ST

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T10CM02138
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/20/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved Project: T10CM02138
8727 E 22nd st
New Modular Bldg


Electrical plans denied for the following:

1. Concerning the SES Load Summary, the new panel loads for Pnl's A and B show 39.9 kva at 360v = 110.8 amps, you show 212.5 amps ? This also makea the total different.
2. Panel shows a 200 amp fuse on #1 conductors ?


Ray T Majuta'
PDSD, City of Tucson,
8/19/10
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
08/20/2010 GERARDO BONILLA OUT TO CUSTOMER Completed