Permit Number: T10CM02118
Parcel: 12801007A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM02118
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/23/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10CM02118
5566 E Broadway #160
TI Retail

Electrical plans denied , all remarks from this review are from changes made to plans.

1. Circuit LPA-1 # 1 has the same number of fixtures as #4, while cir #1 has a total va of 2688, #4 has a total va of 654.
2. Circuit LPA-1 #10 has a total va of 2816 , it only has 12 fixtures at 64 va = 768.
3. Circuit LPA-1 #12 has a total va of 2816 , it only has 12
fixtures at 64 va = 768.
4. All of your lighting circuits have the incorrect loads according to the panel schedule wattages allowed per fixtures.
5. The lighting contactor will have both 227 v circuits as well as 120 v on a 30 amp 300 v lighting contactor ?

Ray T Majuta
Elect Pln Ck,
PDSD City of Tuc,
8/23/10