Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T10CM02118
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/23/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T10CM02118 5566 E Broadway #160 TI Retail Electrical plans denied , all remarks from this review are from changes made to plans. 1. Circuit LPA-1 # 1 has the same number of fixtures as #4, while cir #1 has a total va of 2688, #4 has a total va of 654. 2. Circuit LPA-1 #10 has a total va of 2816 , it only has 12 fixtures at 64 va = 768. 3. Circuit LPA-1 #12 has a total va of 2816 , it only has 12 fixtures at 64 va = 768. 4. All of your lighting circuits have the incorrect loads according to the panel schedule wattages allowed per fixtures. 5. The lighting contactor will have both 227 v circuits as well as 120 v on a 30 amp 300 v lighting contactor ? Ray T Majuta Elect Pln Ck, PDSD City of Tuc, 8/23/10 Ray.Majuta@tucsonaz.gov |