Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T10CM02118
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/03/2010 | DROBEY1 | FIRE | REVIEW | Needs Review | |
| 08/03/2010 | DROBEY1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 08/03/2010 | DROBEY1 | BUILDING-COMMERCIAL | REVIEW | Passed | |
| 08/03/2010 | DROBEY1 | HC | REVIEW | Needs Review | |
| 08/09/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T10CM02118 5566 E Broadway BL # 160 TI Retail The Electrical Plans have been denied for the following: 1. Panel LPA-1 shows circuit 19 feeding TR-A (transformer) on a 175 amp circuit breaker, the one line diagram shows the transformer being fed from a different Panel Section-- LPA-2 . Correct to show feed from correct location.. 2. The transformer is to show a load (va) under each phase for the loads being used on the 120/208 3 phase side . 3. Fixtures on fixture schedule are showing 277 volt while they are conneced to panel C, on 20 amp circuits at 120 volts. 3. The circuits assigned to the lighting contactors appear to be incorrect, for example, the sign lighting contactor (C3), shows circuits C- 2.4.6.8 while they are shown as spares in Panel C schedule. 4. Some lighting circuits in Panel C such as 19,21,20,28,2426,28and 30 are showing loads over 20 amps on 20 amp circuits. 5. Concerning the Load summary on Sheet E-3, is the 600 amp SES feeding off a 800 amp SES, you show a 800 amp and a 600 amp SES. 6. Provide the connected load for Panel LPA-1. Suggest the electrical design be per an EE. Ray T Majuta Elect Pln CK, PDSD, City of Tuc. 8/10/10 Ray.Majuta@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/11/2010 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 08/11/2010 | SUE REEVES | REJECT SHELF | Completed |